Control Output Group continued
Parameters
=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.11
ON
Operation Group
Monitor
Operation Mode ......................................... 5.11
Use
Operation Mode ......................................... 5.11
User Set Point ........................................... 5.12
Manual Output Power .............................. 5.12
Operation Group – Monitor
Operation Mode
• Monitor the operation mode. Normally follows the user selected
mode. It returns to the previous state after an error clears.
• Read only
• Modbus: 200
Range
0: off
1: auto
2: manual control (user selected)
3: manual control (due to error)
Default
auto
Active
always
Operation Group – Use
User Operation Mode
• Select whether the controller is under auto or manual control.
• Read/write
• Modbus: 301
Range
0: auto
1: manual
Default
0: auto
Active
always
Affects
Manual Output Power (Operation Group) manual or manual due
to error
ç
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Non-
volatile Memory
(System Group).