Parameters
=Read Only; =Read/Write; =Turn On/Off Watlow MicroDIN 5.7
ON
Filter Time Constant
• Set the filter time for the input, in seconds. This smooths out a
rapidly changing input signal. Positive values affect the monitor
readings only. Negative values affect both the monitor readings
and the control values.
• Read/write
• Modbus: 604
Range
-60.0 to 60.0
Default
0.0
Active
always
Input Error Action
• Select how the controller responds to an input error.
• Read/write
• Modbus: 902
Range
0: bumpless transfer (control output power remains constant,
see Chapter 5)
1: switch to the Fixed Manual Output (Control Output Group)
setting
2: shut off output
Default
0: bumpless transfer
Active
always
Input Group continued