Chapter 12: Function Blocks LogicPro Users Guide
198 Watlow Anafaze Doc.# 28002-00 Rev 3.00
Digital_Out_206x
The Digital_Out_206x driver supports the relay outputs on the PPC-
206x Digital Out series modules.
To associate a variable with a relay output:
1. Open the Add Program/Resource Variable dialog box.
2. Enter a unique variable Name.
3. Select BOOL from the Type list.
4. Select Output by clicking the check box.
5. Select Digital_Out_206x from the IO Driver list.
6. Select BIT from the IO Size list.
7. Enter the IO Physical Address. The address is:
X.Z X is the module address (41-46)
Z is the module I/O number (1-16)
8. Click [OK].
PPC-206x Digital Out Addressing Example
To create a variable named Relay_6 that sets the state of the 6
th
output on a PPC-206x module with its rotary address switch set to
41, set the options in the Add Program/Resource Variable
dialog box as illustrated below.