Chapter 15: Downloading & Monitoring LogicPro User’s Guide
236 Watlow Anafaze Doc.# 28002-00 Rev 3.00
NOTE! The port is identified when setting up a resource.
The port must be set correctly before building and
compiling executable code for a resource. See
Editing a Resource on page 36 in order to verify or
change the communications port selection.
4. Select Execution menu.
5. Select Build All and Run
– or –
Click on the [Build All and Run] tool. This will build
the runtime executable, download it to the target control-
ler and run your logic control program.
6. The Downloading dialog box will open during the
download displaying transfer statistics and any errors en-
countered.
7. You can start and stop the run time executable by click-
ing the [Start Executable] tool
– or –
[Terminate] tool.
Alternatively, if a runtime executable has already been built:
1. If downloading to a PPC-2000 controller:
a. Set the control mode for each channel to Off.
b. Set each alarm to Disabled.
2. If downloading to a CPC400 controller, note any alarms.
Once downloading commences, all alarms are automati-
cally acknowledged.
ç
CAUTION! Input readings during downloads are not accurate
and may vary widely due to allocation of CPU re-
sources for downloading. Stopping closed loop
control and disabling alarms ensures that outputs
remain off during download.
3. Select the Execution menu.
4. Select Download and Run
– or –
Click the [Download and Run] tool on the Standard
toolbar to just download the runtime executable to the
controller and run your logic control program.