LogicPro Users Guide Chapter 12: Function Blocks
Doc.# 28002-00 Rev 3.00 Watlow Anafaze 197
Analog_Out_205x
The Analog_Out_205x driver supports the outputs on the PPC-205x
series Analog Output modules.
To associate a variable with an analog output:
1. Open the Add Program/Resource Variable dialog box.
2. Enter a unique variable Name.
3. Select INT from the Type list.
4. Select Output by clicking the check box.
5. Select Analog_Out_205x from the IO Driver list.
6. Select WORD from the IO Size list.
7. Enter the IO Physical Address. The address is:
X.Z X is the module address (31-34)
Z is the module I/O number (1-8)
8. Click [OK].
PPC-205x Analog Out Addressing Example
To create a variable named VoltsOut_2 that sets the level of the
second output on a PPC-205x module with its rotary address switch
set to 31, set the options in the Add Program/Resource Variable
dialog box as illustrated below.