Silver Series OIT 4 Watlow Addendum
Chapter 2: Install and Wiring
Consult the Silver Series Installation and Operation Manual for detailed information on installing and
wiring the OITs. This chapter provides important additional information regarding connecting to and
communicating with Watlow controllers.
Connecting via Modbus RTU (232/485)
The tables below indicate to which pins on the Silver Series OIT’s DB9 connectors the Watlow EZ-
ZONE
®
screw terminals should connect.
Connecting via 485 2-wire
Watlow Cable
1
Watlow EZ-ZONE
TS00-0043-0000
TS00-0043-E000
TS00-0070-0000
TS00-0100-0000
1
Supports COM1 only. Cable part number: 0219-0374-0000 for TS00-0070-0000 and TS00-0100-0000
or part number 0219-0388-0000 for TS00-0043-0000 and TS00-0043-E0000
Connecting via 232
Watlow EZ-ZONE
TS00-0043-0000
TS00-0043-E000
TS00-0070-0000
TS00-0100-0000
Connecting via Modbus TCP (Ethernet)
With standard Ethernet cables connect the controller(s) and the Silver Series OIT to an Ethernet switch
or connect the controller directly to the OIT.
Determining or Setting the OIT’s IP Address
If you connect the OIT to an Ethernet network in order to download programs or communicate with
controllers via Ethernet, you must ensure the OIT has a unique IP address and you will need to know
that address in order to communicate from your PC with the OIT.
To read or set the OIT’s IP address:
• Connect a USB mouse to the OIT, if desired and supported.
• Apply power to the OIT.
• Once the OIT is powered up, click the lower right corner of the OIT screen.
• When the button with the arrow or angle bracket appears, click it.
• On the menu bar click the setting button (the one with the wrench or gear icon).
• Enter the password. (By default this is 111111.)