Note:
The controls transformer must
be on the same phase as the
load. See wiring diagram. All
hot lines to the transformer
should be fused at 1 amp with
the proper line voltage.
For manual control, a 1KΩ
potentiometer may be connected
to the AT card input terminals.
Watlow offers a Manual Control
Kit, P/N 08-5362. Using this
potentiometer requires removing
the 5KΩ, R2 resistor for higher
impedance.
Bias and gain adjustment is
required when changing from 4-
20mA input to a manual control
input or a voltage input.
Wiring Diagram for VPAC-AT
Remote Mount Transformer