Watlow Series SD6 Limit with DeviceNet ■ 8 ■
Table 15. Connection Object Instance Attributes
Attribute # Access Rule Name DeviceNet Data
Type
Description of
Attribute
Semantics of Values
1 Get State USINT State of the object
2 Get Instance Type USINT Indicates either
I/O or Messaging
3 Get Transport Class
Trigger
BYTE Defines behaviour
of the Connection
4 Get Produced
Connection ID
UINT Placed in CAN
Identifier Field
when the
Connection trans-
mits
5 Get Consumed
Connection ID
UINT CAN Identifier
Field value that
denotes message to
be received
6 Get Initial Comm
Characteristics
BYTE Defines the
Message Group(s)
across which pro-
ductions and con-
sumption associat-
ed with this
Connection when it
occurs
7 Get Produced
Connection Size
UNIT Maximum number
of bytes transmit-
ted across this
Connection
8 Get Consumed
Connection Size
UNIT Maximum number
of bytes received
across this
Connection
9 Get/Set Expected
Packet Rate
UNIT Will round up to
the next 100 mSec.
Increment.
12 Get/Set
(set for
explicit
messaging
only)
Watchdog
Timeout Action
USINT Defines how to
handle
Inactivity/Watchdo
g timeouts
For Explicit
Connection only:
1 = Auto Delete
3 = Deferred
Delete