Setup
Setup Menu, Chapter 4 WATLOW Series 988LF Users Manual 4.9
[`Ot2]
Output 1
Set the way that output 1 will respond to a difference between the set
point and an input variable.
[``Ht](Heat) select reverse action, so that output 1 responds when the
input signal is less than the setpoint.
[``CL](Cool) select direct action, so that output 1 responds when the
input signal is more than the setpoint.
[`Ot1] This prompt always appears.
Default
[``Ht] [``CL]
[`Ot1] [`Ot1]
Process 1
Select the process range for output 1.
[Prc1] This prompt appears only on controllers equipped with output 1
process hardware (98__-__F_-___).
Default
4-20mA 0-20mA 0-5VÎ 1-5VÎ 0-10VÎ (dc)
[4-20] [0-20] [`0-5] [`1-5] [0-10]
[Prc1] [Prc1] [Prc1] [Prc1] [Prc1]
Output 2
Selects the secondary output action
[``AL] de-energizes output 2 in an alarm condition.
[`ALn] energizes output 2 in an alarm condition.
[``Ht](Heat) selects reverse action, so that output 2 responds when the
input signal is less than the set point.
[``CL](Cool) selects direct action, so that output 2 responds when the
input signal is more than the set point.
[`Ot2] This prompt appears only on controllers equipped with output 2
hardware (not 98_L-___A-AA__).
Default
[``no] [``AL] [`Aln] [``Ht] [``CL]
[`Ot2] [`Ot2] [`Ot2] [`Ot2] [`Ot2]
[`Ot1]
[Prc1]