5) For PLC name choose
the Modbus Master or
Modbus TCP/IP
Master.
6) For Device type
choose 4x.
(075)
7) For Address enter the
address of the heat
power for your
controller. See the
table.
8) Select the data type in
the field below the
Address field. See the
table.
9) Click OK.
For this
controller…
This
parameter…
Enter this
Address*…
Choose this
Data Type…
RMCxxxx-xxxxxxx
Heat Power
2245
32-bit Float
RMHx-xxxx-x1xx
Heat Power
4125
32-bit Float
PMxxxxx-xxxxxxx
Heat Power
1905
32-bit Float
STxx-xxMx-xxxx
Heat Power
237
32-bit Float
ST via RUI Gateway
Heat Power
1901
32-bit Float
Other Controllers
Consult the controller manual.
*These addresses have already been changed to the absolute form
required for EZwarePlus by adding 1 to the value listed in the Watlow
manual. Enter them as listed
Silver Series EM OIT 16 Watlow Addendum