Chapter 2: Installation CPC400 Series User’s Guide
38 Watlow Anafaze Doc. 0600-2900-2000
TB50 Connections
Table 2.6 TB50 Connections
1
The indicated outputs are dedicated for control when enabled in the
loop setup. If one or both of a loop’s outputs are disabled, the corre-
sponding digital outputs become available for alarms or programmable
logic.
2
If you install a Watlow Anafaze Serial DAC, the CPC400 uses digital
output 34 (terminal 10) for a clock line. You cannot use output 34 for
anything else if a Serial DAC is installed.
Control Output
1
Control Output
1
Ter-
minal
Function CPC408 CPC404
Ter-
minal
Function CPC408 CPC404
1
+5VÎ (dc)
2
+5VÎ (dc)
3 CTRL COM 4 CTRL COM
5 Not Used 6 Watchdog
Timer
7 Pulse Input 8 Global Alarm
9 Output 1 Loop 1 heat Loop 1 heat 10
Output 34
2
11 Output 2 Loop 2 heat Loop 2 heat 12 Output 33
13 Output 3 Loop 3 heat Loop 3 heat 14 Output 32
15 Output 4 Loop 4 heat Loop 4 heat 16 Output 31
17 Output 5 Loop 5 heat Pulse loop
heat
18 Output 30
19 Output 6 Loop 6 heat Loop 1 cool 20 Output 29
21 Output 7 Loop 7 heat Loop 2 cool 22 Output 28
23 Output 8 Loop 8 heat Loop 3 cool 24 Output 27
25 Output 9 Pulse loop
heat
Loop 4 cool 26 Output 26
27 Output 10 Loop 1 cool Pulse loop
cool
28 Output 25
29 Output 11 Loop 2 cool 30 Output 24
31 Output 12 Loop 3 cool 32 Output 23
33 Output 13 Loop 4 cool 34 Output 22
35 Output 14 Loop 5 cool 36 Output 21
37 Output 15 Loop 6 cool 38 Output 20
39 Output 16 Loop 7 cool 40 Output 19
41 Output 17 Loop 8 cool 42 Output 18 Pulse loop
cool
43 Input 1 44 Input 2
45 Input 3 46 Input 4
47 Input 5 48 Input 6
49 Input 7 50 Input 8