Watlow 8LS Controller Uživatelský manuál Strana 109

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 140
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 108
Appendix A: Ramp Soak
8LS Users Guide 101
Running several profiles simultaneously
To run several profiles simultaneously, follow these steps:
1. Setup the profiles so that segment 1 of each profile has the same
latched trigger.
2. Assign the profiles to the appropriate loops. The loops will go to the
Ready segment of each profile.
3. Set each profile to Run mode.
4. Trip the trigger.
Editing a profile while it is running
You can edit a profile while it is running, but the changes you have
made will not take effect until the next time it runs.
Ramp/Soak Displays
The Single loop and Bar Graph displays show additional codes for R/S
controllers.
Single loop display
When the controller is running a profile, the Single Loop display shows
the profile mode where it would usually show MAN or AUTO. The next
table shows the available codes and their meaning.
This is the Single Loop display when a profile is running.
Code Mode
STRT The profile is in the Ready segment.
RUN The profile is running.
HOLD The user has put the profile in Hold mode.
TOHO The profile is in tolerance hold.
WAIT The profile is in trigger wait state.
1234 56 78
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUTPUT%
3 73 F
73 S 0
Loop number
Process variable
En
g
ineerin
g
units
Setpoint
Profile mode
Output percenta
g
e
Zobrazit stránku 108
1 2 ... 104 105 106 107 108 109 110 111 112 113 114 ... 139 140

Komentáře k této Příručce

Žádné komentáře