CAS200
User’s Guide
WATLOW
1241 Bundy Boulevard
Winona, MN 55987
Phone: +1 (507) 454-5300. Fax: +1 (507) 452-4507
Document No. 0600-3050-2400. Revision A
November 2008
Zobrazit stránku 0
1 2 3 4 5 6 ... 123 124

Shrnutí obsahu

Strany 1 - User’s Guide

CAS200 User’s Guide WATLOW 1241 Bundy BoulevardWinona, MN 55987Phone: +1 (507) 454-5300. Fax: +1 (507) 452-4507Document No. 0600-3050-2400. Revisio

Strany 2 - Warranty

List of Figures CAS200 User’s Guideviii Watlow Anafaze 7 Specifications 91 Figure 7.1— CAS200 Processor Module Dimensions 92Figure 7.2— CAS200 Cl

Strany 3 - Contents

Chapter 6: Linear Scaling Examples CAS200 User’s Guide88 Watlow Anafaze Example 1: 4-20mA Sensor SituationA pressure sensor that generates a 4-20 m

Strany 4 - Setup 41

CAS200 User’s Guide Chapter 6: Linear Scaling ExamplesWatlow Anafaze 89 Example 2: 0-5Vdc Sensor SituationA flow sensor connected to the scanner me

Strany 5 - Setup Channel Alarms 58

Chapter 6: Linear Scaling Examples CAS200 User’s Guide90 Watlow Anafaze Example 3: Pulse Encoder SituationA pulse encoder which measures the moveme

Strany 6 - Contents CAS200 User’s Guide

Watlow Anafaze 917SpecificationsThis chapter contains specifications for the CAS200 series scanners, TB50 terminal board and the CAS200 power supply.

Strany 7 - Watlow Anafaze v

Chapter 7: Specifications CAS200 User’s Guide92 Watlow Anafaze CAS200 Processor Physical SpecificationsTable 7.2 Environmental SpecificationsTable 7

Strany 8

CAS200 User’s Guide Chapter 7: Specifications Watlow Anafaze 93Table 7.4 Processor with Straight SCSIFigure 7.2 CAS200 Clearances with Straight SCSI

Strany 9 - List of Figures

Chapter 7: Specifications CAS200 User’s Guide94 Watlow AnafazeTable 7.6 Processor ConnectionsPower Terminals (TB2) Captive screw cage clampPower Wire

Strany 10 - 7 Specifications 91

CAS200 User’s Guide Chapter 7: Specifications Watlow Anafaze 95 TB50 Physical SpecificationsTable 7.7 TB50 Physical DimensionsFigure 7.4 TB50 Dimen

Strany 11 - List of Tables

Chapter 7: Specifications CAS200 User’s Guide96 Watlow AnafazeTable 7.9 TB50 with Straight SCSIFigure 7.5 TB50 Dimensions with Straight SCSI CableLeng

Strany 12

CAS200 User’s Guide Chapter 7: Specifications Watlow Anafaze 97Table 7.10 TB50 with Right Angle SCSIFigure 7.6 TB50 Dimensions with Right-Angle SCSI

Strany 13 - System Overview

Watlow Anafaze ix List of Tables 2 Installation Table 2.1— Cable Recommendations 16Table 2.2— Power Connections 20Table 2.3— EIA/TIA-232 Connect

Strany 14 - Getting Started

Chapter 7: Specifications CAS200 User’s Guide98 Watlow Anafaze Inputs The scanner accepts analog sensor inputs which are measured and may be used as

Strany 15 - Product Features

CAS200 User’s Guide Chapter 7: Specifications Watlow Anafaze 99Table 7.12 Pulse InputsTable 7.13 Thermocouple Range and Resolution* True for 10% to 1

Strany 16 - Parts List

Chapter 7: Specifications CAS200 User’s Guide100 Watlow AnafazeTable 7.14 Input Resistance for Voltage InputsTable 7.15 Digital Inputs Range Input Res

Strany 17 - Safety

CAS200 User’s Guide Chapter 7: Specifications Watlow Anafaze 101 OutputsThe scanner provides open-collector outputs. These outputs are typically us

Strany 18 - 6 Watlow Anafaze

Chapter 7: Specifications CAS200 User’s Guide102 Watlow AnafazeTable 7.18 5Vdc Output (Power to Operate Solid State Relays)Table 7.19 Reference Voltag

Strany 19 - Installation

CAS200 User’s Guide Chapter 7: Specifications Watlow Anafaze 103 CAS200 Power Supply&RPSOHWHVSHFLILFDWLRQVIRUWKH&$6SRZHUVXSSO\DUH

Strany 20 - Typical Installation

Chapter 7: Specifications CAS200 User’s Guide104 Watlow Anafaze

Strany 21 - External Safety Devices

Watlow Anafaze 105GlossaryAACSee Alternating Current.AC Line FrequencyThe frequency of the AC power line measuredin Hertz (Hz), usually 50 or 60Hz.Acc

Strany 22 - Mounting

Glossary CAS200 User’s Guide106 Watlow AnafazeCCalibrationThe comparison of a measuring device (anunknown) against an equal or better standard.Celsius

Strany 23 - Mounting the Scanner

CAS200 User’s Guide GlossaryWatlow Anafaze 107Deutsche Industrial Norms (DIN)A set of technical, scientific and dimensionalstandards developed in Germa

Strany 24 - 12 Watlow Anafaze

List of Tables CAS200 User’s Guidex Watlow Anafaze Table 7.14— Input Resistance for Voltage Inputs 100Table 7.15— Digital Inputs 100Table 7.16— D

Strany 25 - Mounting the TB50

Glossary CAS200 User’s Guide108 Watlow AnafazeFrequencyThe number of cycles over a specified period oftime, usually measured in cycles per second.Also

Strany 26 - System Wiring

CAS200 User’s Guide GlossaryWatlow Anafaze 109Linear InputA process input that represents a straight linefunction.LinearityThe deviation in response f

Strany 27 - Wiring Recommendations

Glossary CAS200 User’s Guide110 Watlow AnafazeOutput TypeThe form of PID control output, such as TimeProportioning, Distributed Zero Crossing,SDAC, or

Strany 28 - Noise Suppression

CAS200 User’s Guide GlossaryWatlow Anafaze 111Resistance Temperature Detector (RTD)A sensor that uses the resistance temperaturecharacteristic to meas

Strany 29 - Avoiding RFI/EMI

Glossary CAS200 User’s Guide112 Watlow AnafazeTI (Timed Integral)The Integral term.TransmitterA device that transmits temperature data fromeither a th

Strany 30 - Ground Loops

Watlow Anafaze 1 1 System Overview Manual Contents This manual describes how to install, setup, and operate a CAS200. Included are six chapters and

Strany 31 - Power Connections

Chapter 1: System Overview CAS200 User’s Guide2 Watlow Anafaze Getting Started The following sections provide information regarding product features

Strany 32 - Table 2.2 Power Connections

CAS200 User’s Guide Chapter 1: System OverviewWatlow Anafaze 3 Product Features The CAS200 is a modular monitoring system with 16 analog inputs. It

Strany 33 - NO" key while

Chapter 1: System Overview CAS200 User’s Guide4 Watlow Anafaze Pulse Counter Input: Use the pulse counter input for precise monitoring of motor or b

Strany 34 - Input Wiring

CAS200 User’s Guide Chapter 1: System OverviewWatlow Anafaze 5 Mounting Scanner Components Install the scanner in a location free from excessive h

Strany 35 - Thermocouple Connections

Chapter 1: System Overview CAS200 User’s Guide6 Watlow Anafaze

Strany 36 - Current Input Connections

Watlow Anafaze 7 2 Installation This chapter describes how to install the CAS200 series scanner and its peripherals. Installation of the scanner invo

Strany 37 - Serial Communications

Copyright © 2001Watlow Anafaze Information in this manual is subject to change without notice. No part of this publi-cation may be reproduced, stor

Strany 38 - EIA/TIA-485 Interface

Chapter 2: Installation CAS200 User’s Guide8 Watlow Anafaze Typical Installation The illustrations below show typical installations of the scanner w

Strany 39 - Cable Recommendations

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 9 Safety∫ WARNING! Ensure that power has been shut off to your entire process before you b

Strany 40 - Termination

Chapter 2: Installation CAS200 User’s Guide10 Watlow Anafaze Mounting We recommend you mount the scanner in a panel not more than 0.2 inches thick.

Strany 41 - Wiring Digital I/O

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 11 Other Tools: You will also need these tools:• Phillips head screwdriver• Flathead screw

Strany 42 - Digital Outputs

Chapter 2: Installation CAS200 User’s Guide12 Watlow Anafaze Steps Using the Collar BracketInstalling and mounting requires access to the back of th

Strany 43 - Alarm Output Connections

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 13 Mounting the TB50There are two ways you can mount the TB50, by using the pre-installed

Strany 44 - Digital Inputs

Chapter 2: Installation CAS200 User’s Guide14 Watlow AnafazeFigure 2.6 Mounting Dimensions System WiringSuccessful installation and operation of the a

Strany 45 - Watlow Anafaze 33

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 15çCAUTION! Do not wire bundles of low-voltage signal and control circuits next to bundles o

Strany 46 - Table 2.6 TB18 Connections

Chapter 2: Installation CAS200 User’s Guide16 Watlow AnafazeTable 2.1 Cable Recommendations Noise Suppression The CAS200’s outputs are typically use

Strany 47 - Using the CAS200

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 17 Avoiding RFI/EMITo avoid or eliminate most RFI/EMI noise problems:• Connect the CAS200

Strany 48 - Front Panel Keys

Watlow Anafaze i Contents List of Figures ixList of Tables xiiiSystem Overview 1 Manual Contents 1Getting Started 2 Safety symbols 2Contactin

Strany 49 - Watlow Anafaze 37

Chapter 2: Installation CAS200 User’s Guide18 Watlow Anafaze Ground LoopsGround loops occur when current passes from the process through the scanner

Strany 50 - Job Display

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 19 Power ConnectionsFigure 2.7 CAS200 Series Scanner Wiring the Power SupplyçCAUTION! Use

Strany 51 - Change Setpoint

Chapter 2: Installation CAS200 User’s Guide20 Watlow AnafazeFigure 2.8 Power Connections with the CAS200 Power SupplyTable 2.2 Power Connections1.

Strany 52 - Resetting an Alarm

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 215. A third Ground connector on TB2 is available for chas-sis ground. This terminal is conn

Strany 53 - Watlow Anafaze 41

Chapter 2: Installation CAS200 User’s Guide22 Watlow Anafaze3. Press "Y" for Yes to reset all the parameters. When all parameters are res

Strany 54 - How to Edit a Menu

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 23The scanner accepts the following inputs without any special scaling resistors:• J, K, T,

Strany 55 - Single Channel Display

Chapter 2: Installation CAS200 User’s Guide24 Watlow Anafaze∫WARNING! The scanner uses a floating ground system. Therefore, isolate input devices or h

Strany 56 - Load a Job

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 25NOTE! When mixing current inputs with low voltage in-puts (thermocouples or voltage inputs

Strany 57 - Job Select Inputs

Chapter 2: Installation CAS200 User’s Guide26 Watlow Anafazeto their request to send (RTS) signal, or a data set ready (DSR) in response to their data

Strany 58 - Startup Alarm Delay

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 27Figure 2.14 EIA/TIA-485 Wiring Cable RecommendationsWatlow Anafaze recommends Belden 984

Strany 59 - Communications Baud Rate

Contents CAS200 User’s Guideii Watlow Anafaze Wiring the Power Supply 19Testing Power to the Scanner 21Connecting the TB50 to the CAS200 22 Input Wir

Strany 60 - Communications Protocol

Chapter 2: Installation CAS200 User’s Guide28 Watlow AnafazeFigure 2.15 Recommended System Connections Signal CommonFor usual installations, do not

Strany 61 - Digital Output Polarity

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 29 EIA/TIA-485 Converters and Laptop ComputersFor a 232-to-485 converter to optically isol

Strany 62 - Setup Channel Inputs

Chapter 2: Installation CAS200 User’s Guide30 Watlow Anafaze Avoiding Noise ProblemsTo avoid noise problems be sure ground wire terminal (on TB2) is

Strany 63 - Display Resolution

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 31Figure 2.16 Wiring Digital Outputs Alarm Output ConnectionsTypical alarm outputs use ext

Strany 64 - Input Units

Chapter 2: Installation CAS200 User’s Guide32 Watlow Anafaze CPU WatchdogThe CPU watchdog monitors the microprocessor. Its sink output is located on

Strany 65 - Input Reading Offset

CAS200 User’s Guide Chapter 2: InstallationWatlow Anafaze 33Figure 2.19 Wiring Digital InputsTable 2.5 TB50 Connections for CAS200Terminal Function Te

Strany 66 - Linear Scaling Menus

Chapter 2: Installation CAS200 User’s Guide34 Watlow AnafazeTable 2.6 TB18 ConnectionsTerminal Function1 +5 Vdc2 CTRL COM3 Watchdog timer4 Global alar

Strany 67 - Display Format

Watlow Anafaze 353Using the CAS200 Introduction This chapter will show you how to use the CAS200 from the front panel. The next diagram shows how to r

Strany 68 - Input Scaling High Reading

Chapter 3: Using the CAS200 CAS200 User’s Guide36 Watlow Anafaze Front PanelThe front panel provides a convenient interface with the CAS200 system. Yo

Strany 69 - Input Filter

CAS200 User’s Guide Chapter 3: Using the CAS200 Watlow Anafaze 37∫WARNING! The NO-key reset clears the system's memoryand reinitializes the CAS2

Strany 70 - Setup Channel Alarms

CAS200 User’s Guide ContentsWatlow Anafaze iii Job Select Input Polarity 46Startup Alarm Delay 46Keyboard Lock Status 47Scanner Address 47Communicati

Strany 71 - Watlow Anafaze 59

Chapter 3: Using the CAS200 CAS200 User’s Guide38 Watlow AnafazePress Change SP to change the setpoints.The FUNC key is not used in normal operation.

Strany 72 - High Process Alarm Type

CAS200 User’s Guide Chapter 3: Using the CAS200 Watlow Anafaze 39When you load a job, Job display shows you this screen:If you remotely loaded the jo

Strany 73 - High Deviation Alarm Type

Chapter 3: Using the CAS200 CAS200 User’s Guide40 Watlow Anafaze AlarmsIf an alarm occurs, an eight character alarm code is displayed in the lower-rig

Strany 74 - Low Deviation Alarm Type

Watlow Anafaze 414Setup CAS200 MenusThe Setup menus let you change detailed configuration information. How to Enter the Setup Menus1. In Single Cha

Strany 75 - Low Process Alarm Type

Chapter 4: Setup CAS200 User’s Guide42 Watlow Anafaze How to Edit a Menu• Press Yes to select the menu or No to advance to the next menu.• Press Yes

Strany 76 - Alarm Deadband

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 43CHNGSPPasskey SequenceSingle Channel DisplaySetup GlobalParametersENTERALARMACKCom Protocol(Ana,

Strany 77 - Manual I/O Test

Chapter 4: Setup CAS200 User’s Guide44 Watlow Anafaze Setup Global Parameters MenuThe setup global parameters menu looks like this. Load a JobSelec

Strany 78 - Keypad Test

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 45 Save Setup to JobUse this menu to save job information for every channel, to one of eight jobs

Strany 79 - When There is a Problem

Chapter 4: Setup CAS200 User’s Guide46 Watlow AnafazeSelectable values: 1, 2, or 3 inputs, or None. These choices have the following effect: Job Sel

Strany 80 - Troubleshooting Scanners

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 47 Keyboard Lock StatusThis selection lets you lock the front panel operator function key, Change

Strany 81 - System Alarms

Contents CAS200 User’s Guideiv Watlow Anafaze Low Process Alarm Setpoint 63Low Process Alarm Type 63Low Process Alarm Output Number 63Alarm Deadband

Strany 82 - Other Behaviors

Chapter 4: Setup CAS200 User’s Guide48 Watlow Anafaze Communications ProtocolThis menu is located under the Setup Global Parameters main menu. It al

Strany 83 - Battery Dead

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 49 AC Line FrequencyThis menu lets you configure the scanner to match an AC line frequency of 50

Strany 84 - HW Gain or Offset Failure

Chapter 4: Setup CAS200 User’s Guide50 Watlow Anafaze EPROM InformationThis view-only display shows the scanner's EPROM version and checksum.

Strany 85 - Checking Analog Inputs

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 51NOTE! If you set the input type to Skip, you won't see anyof the other submenus in the Setup

Strany 86 - Earth Grounding

Chapter 4: Setup CAS200 User’s Guide52 Watlow Anafaze Pulse Sample TimeYou can connect a digital pulse signal of up to 2KHz to the scanner's pu

Strany 87 - Testing Digital Outputs

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 53 Input Reading OffsetThis menu lets you set an input reading offset function to make up for the

Strany 88 - Supervised Systems

Chapter 4: Setup CAS200 User’s Guide54 Watlow Anafaze Linear Scaling MenusThe linear scaling menus appear under the Setup Channel Inputs main menu.

Strany 89 - Communications

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 55The PV (Process Variable) range for the scaled input is between the PV values that correspond to

Strany 90 - NO-Key Reset

Chapter 4: Setup CAS200 User’s Guide56 Watlow Anafaze High Process ValueFrom this menu, you can enter a high process value. The high process value a

Strany 91 - Replacing the EPROM

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 57 Input Scaling Low ReadingUse this menu to enter the input level that corresponds to the low pr

Strany 92 - 80 Watlow Anafaze

CAS200 User’s Guide ContentsWatlow Anafaze v Linear Scaling Examples 87 Example 1: 4-20mA Sensor 88 Situation 88Setup 88 Example 2: 0-5Vdc Sensor 89

Strany 93 - Changing Communications

Chapter 4: Setup CAS200 User’s Guide58 Watlow Anafaze Setup Channel AlarmsThe Setup Channel Alarms menu lets you access menus which change alarm func

Strany 94 - CAS200 Input Circuit

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 59• Any digital output can be assigned to one or more process variable alarms. The output is active

Strany 95 - CAS200 Current Inputs

Chapter 4: Setup CAS200 User’s Guide60 Watlow Anafaze Alarm DelayYou can set the CAS200 to delay normal alarm detection and alarm reporting. There a

Strany 96 - CAS200 Voltage Inputs

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 61 High Process Alarm Output NumberThis menu lets you choose the digital output that activates wh

Strany 97 - Scaling and Calibration

Chapter 4: Setup CAS200 User’s Guide62 Watlow Anafaze High Deviation Alarm Output NumberThis menu assigns a digital output which activates when the

Strany 98 - 86 Watlow Anafaze

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 63 Low Process Alarm SetpointThis menu is used to set a low process alarm setpoint. (The low proc

Strany 99 - Linear Scaling Examples

Chapter 4: Setup CAS200 User’s Guide64 Watlow Anafaze Alarm DeadbandThis menu lets you set an alarm deadband. This deadband value applies to the hig

Strany 100 - Example 1: 4-20mA Sensor

CAS200 User’s Guide Chapter 4: SetupWatlow Anafaze 65 Manual I/O TestPress Yes at this prompt to see menus which can help you test the digital inputs

Strany 101 - Example 2: 0-5Vdc Sensor

Chapter 4: Setup CAS200 User’s Guide66 Watlow Anafaze Digital Output TestThis menu lets you manually toggle a digital output On or Off to test it. (

Strany 102 - Example 3: Pulse Encoder

Watlow Anafaze 675Troubleshooting and ReconfiguringThe first sections of this chapter describe general troubleshooting for the CAS200. Later sections

Strany 103 - Specifications

Contents CAS200 User’s Guidevi Watlow Anafaze

Strany 104 - Dimensions

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide68 Watlow AnafazeçCAUTION! Before trying to troubleshoot a problem by replac-ing your

Strany 105 - Watlow Anafaze 93

CAS200 User’s Guide Chapter 5: Troubleshooting and Reconfiguring Watlow Anafaze 69 Thermocouple Break AlarmWhen a thermocouple break alarm occurs,

Strany 106 - 94 Watlow Anafaze

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide70 Watlow Anafaze Other BehaviorsThe following table indicates potential problems wi

Strany 107 - Table 7.8 TB50 Connections

CAS200 User’s Guide Chapter 5: Troubleshooting and Reconfiguring Watlow Anafaze 71 Corrective and Diagnostic ProceduresThe following sections detai

Strany 108 - SCSI Cable

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide72 Watlow Anafaze HW Ambient FailureThe hardware failure ambient alarm indicates tha

Strany 109

CAS200 User’s Guide Chapter 5: Troubleshooting and Reconfiguring Watlow Anafaze 73NOTE! If the scanner has failed, it is likely that it wasdamaged by

Strany 110 - Inputs

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide74 Watlow Anafaze5. To verify that the scanner hardware is working correctly, check an

Strany 111 - Resolution

CAS200 User’s Guide Chapter 5: Troubleshooting and Reconfiguring Watlow Anafaze 75 Testing Output DevicesConnect the solid state relay (SSR) contro

Strany 112 - Table 7.15 Digital Inputs

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide76 Watlow Anafaze Testing Digital Inputs1. Turn off power to the scanner.2. Disconne

Strany 113 - Outputs

CAS200 User’s Guide Chapter 5: Troubleshooting and Reconfiguring Watlow Anafaze 77• To test an EIA/TIA-232 interface, purchase an EIA/TIA-232 tester

Strany 114 - Parameter Description

Watlow Anafaze vii List of Figures 1 System Overview 1 Figure 1.1— System Components 4 2 Installation 7 Figure 2.1— System Components 8Figure 2

Strany 115 - CAS200 Power Supply

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide78 Watlow Anafaze Ground ChannelsMany PC communications ports have their common wire

Strany 116 - 104 Watlow Anafaze

CAS200 User’s Guide Chapter 5: Troubleshooting and Reconfiguring Watlow Anafaze 796. If you do not see the RESET WITH DEFAULTS? promptor do not get a

Strany 117 - Glossary

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide80 Watlow AnafazeFigure 5.1 Removal of Electronics Assembly from Case5. Unscrew the fo

Strany 118 - 106 Watlow Anafaze

CAS200 User’s Guide Chapter 5: Troubleshooting and Reconfiguring Watlow Anafaze 81Figure 5.3 EPROM Location7. Remove the existing EPROM from its sock

Strany 119 - Watlow Anafaze 107

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide82 Watlow AnafazeYou will need tweezers and a Phillips head screwdriver to switch betw

Strany 120 - 108 Watlow Anafaze

CAS200 User’s Guide Chapter 5: Troubleshooting and Reconfiguring Watlow Anafaze 83Figure 5.6 shows the schematic for one single-ended sensor input to

Strany 121 - Watlow Anafaze 109

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide84 Watlow AnafazeTable 5.4 Resistor Locations for CAS200 Current Inputs CAS200 Volta

Strany 122 - 110 Watlow Anafaze

CAS200 User’s Guide Chapter 5: Troubleshooting and Reconfiguring Watlow Anafaze 85Table 5.6 Resistor Locations for CAS200 Voltage Inputs Scaling an

Strany 123 - Watlow Anafaze 111

Chapter 5: Troubleshooting and Reconfiguring CAS200 User’s Guide86 Watlow Anafaze

Strany 124 - 112 Watlow Anafaze

Watlow Anafaze 876Linear Scaling ExamplesThis chapter provides three linear scaling examples. The examples describe:• A pressure sensor generating a 4